PLC profiles

Intro

The slmp-connection node requires one canonical PLC profile. The node uses that value to choose the SLMP frame, PLC series behavior, and address-numbering rules. Use profileDescriptors() from lib/slmp/capability-profiles when an editor or configuration schema needs the canonical name, display name, connection availability, and base-profile relationship in one list. The abstract melsec:qcpu entry is included with connectable: false. This descriptor list is the stable source for selectors; store canonicalName, not displayName.

For cross-profile capability and device-range details, see the SLMP Profile Reference.

The node intentionally does not infer this value from ReadTypeName, model text, or model code. Some PLCs or communication paths cannot return a reliable type name, and a wrong inference can select the wrong address grammar or range catalog. Keep the PLC profile as an explicit human/configuration choice.

Verified hardware available for focused validation is maintained once in the shared MELSEC SLMP profile catalog.

Supported PLC profiles

Canonical profile Display name Frame Notes
melsec:iq-f MELSEC iQ-F (built-in) 3E X and Y addresses use octal numbering. DX and DY are not valid.
melsec:iq-r MELSEC iQ-R (built-in) 4E Default profile used by the examples.
melsec:iq-r:rj71en71 MELSEC iQ-R (RJ71EN71) 4E Ethernet-unit profile using iQ-R compatibility.
melsec:iq-l MELSEC iQ-L (built-in) 4E Use for MELSEC iQ-L targets.
melsec:mx-f MELSEC MX-F (built-in) 4E Use for MELSEC MX-F targets.
melsec:mx-r MELSEC MX-R (built-in) 4E Use for MELSEC MX-R targets.
melsec:mx-r:rj71en71 MELSEC MX-R (RJ71EN71) 4E Ethernet-unit profile based on melsec:mx-r.
melsec:lcpu MELSEC-L (built-in) 3E Q/L-series profile. Use normal read/write flows for typical device access.
melsec:lcpu:lj71e71-100 MELSEC-L (LJ71E71-100) 4E Ethernet unit profile using Q/L compatibility.
melsec:qcpu:qj71e71-100 MELSEC-Q (QJ71E71-100) 4E Ethernet unit profile for QCPU connections.
melsec:qnu MELSEC QnU (built-in) 3E Q/L-series profile. Use normal read/write flows for typical device access.
melsec:qnu:qj71e71-100 MELSEC QnU (QJ71E71-100) 4E Ethernet unit profile using Q/L compatibility.
melsec:qnudv MELSEC QnUDV (built-in) 3E Q/L-series profile. Use normal read/write flows for typical device access.
melsec:qnudv:qj71e71-100 MELSEC QnUDV (QJ71E71-100) 4E Ethernet unit profile using Q/L compatibility.

melsec:qcpu is base-only and is not selectable in the editor. Use melsec:qcpu:qj71e71-100 for QCPU Ethernet unit connections.

How to configure the connection node

Field Example value Description
Host 192.168.250.100 IP address or host name for your PLC.
Port 1025 Use 1025 for TCP examples or 1035 for UDP examples.
Transport tcp Select tcp or udp.
PLC profile melsec:iq-r Select one exact canonical PLC profile from the table above.
The selected profile is always enforced by the public API. Operations known to
be unavailable for that PLC are rejected before sending; there is no public
profile-check bypass.

Every saved connection contains these route fields. The editor initializes a new connection with the following own-station values:

Field Default-style value Description
Network 0 Target network number.
Station 255 Target station number.
Module I/O 03FF Own station module I/O number.
Multidrop 0 Multidrop station number.