Gotchas

Timer/counter preset write returns E1

Field Detail
Symptom A timer or counter preset write returns E1.
Root cause Host Link preset writes through WS and WSS are supported on KV-8000/7000-series, not on KV-3000, KV-5000, or KV-NANO.
Fix Do not write timer/counter presets on unsupported models; use read_timer, read_counter, or read_timer_counter for safe reads.
use plc_comm_hostlink::{HostLinkClient, HostLinkConnectionOptions};

#[tokio::main]
async fn main() -> Result<(), Box<dyn std::error::Error>> {
    let client =
        HostLinkClient::connect(HostLinkConnectionOptions::new("192.168.250.100")).await?;

    let value = client.read_timer_counter("T0").await?;
    println!("{:?}", value);

    client.close().await?;
    Ok(())
}

AT device fails on KV-X500

Field Detail
Symptom Reading AT0 fails or the range catalog reports no AT entry for KV-X500.
Root cause AT is not available in keyence:kv-x500 or keyence:kv-x500-xym.
Fix Check the selected profile before using AT, and avoid AT on KV-X500 projects.
use plc_comm_hostlink::device_range_catalog_for_plc_profile;

fn main() -> Result<(), Box<dyn std::error::Error>> {
    let catalog = device_range_catalog_for_plc_profile("keyence:kv-x500")?;
    println!("{:?}", catalog.entry("AT"));
    Ok(())
}

X or Y address rejected

Field Detail
Symptom X or Y raises an address parse or PLC device-number error.
Root cause X and Y use decimal-bank plus hex-bit notation. X10F means bank 10, bit F.
Fix Use X10F or Y10F, and select an -xym profile when you want XYM aliases.
use plc_comm_hostlink::HostLinkAddress;

fn main() -> Result<(), Box<dyn std::error::Error>> {
    let address = HostLinkAddress::normalize("X10F")?;
    println!("{address}");
    Ok(())
}

R, MR, LR, or CR address rejected

Field Detail
Symptom R, MR, LR, or CR raises an address parse or PLC device-number error.
Root cause These families use KEYENCE two-digit bit notation.
Fix Use forms such as R200 or MR100; do not treat the full suffix as one hexadecimal number.
use plc_comm_hostlink::HostLinkAddress;

fn main() -> Result<(), Box<dyn std::error::Error>> {
    let address = HostLinkAddress::normalize("MR100")?;
    println!("{address}");
    Ok(())
}

Wrong port causes an immediate timeout

Field Detail
Symptom The connection times out immediately even though the PLC responds on the network.
Root cause KV Host Link uses port 8501, not the SLMP/Computerlink port 1025.
Fix Set options.port = 8501 or leave the default from HostLinkConnectionOptions::new.
use plc_comm_hostlink::HostLinkConnectionOptions;

fn main() {
    let mut options = HostLinkConnectionOptions::new("192.168.250.100");
    options.port = 8501;
    println!("{}", options.port);
}

Non-canonical profile string rejected

Field Detail
Symptom A display label, uppercase variant, or old alias returns HostLinkError.
Root cause The range catalog accepts only exact canonical profile strings. It does not infer the profile from a PLC model response.
Fix Store the canonical string from PROFILES.md in your project settings or UI value.
use plc_comm_hostlink::available_plc_profiles;

fn main() {
    for profile in available_plc_profiles() {
        println!("{profile}");
    }
}

DM100.D reads the wrong thing

Field Detail
Symptom DM100.D reads a boolean-like value instead of a 32-bit value.
Root cause Dot notation means bit-in-word, so DM100.D is bit 13, not a double-word read.
Fix Use the dtype argument or colon notation for data types.
use plc_comm_hostlink::{HostLinkClient, HostLinkConnectionOptions};

#[tokio::main]
async fn main() -> Result<(), Box<dyn std::error::Error>> {
    let client =
        HostLinkClient::connect(HostLinkConnectionOptions::new("192.168.250.100")).await?;

    let value = client.read_typed("DM100", "D").await?;
    println!("{:?}", value);

    client.close().await?;
    Ok(())
}

CTH or CTC address rejected

Field Detail
Symptom CTH or CTC appears in the catalog but fails as an input address.
Root cause CTH and CTC are catalog metadata rows for supported profiles, while the current address parser does not accept them as input addresses.
Fix Treat them as catalog metadata only.
use plc_comm_hostlink::device_range_catalog_for_plc_profile;

fn main() -> Result<(), Box<dyn std::error::Error>> {
    let catalog = device_range_catalog_for_plc_profile("keyence:kv-5000")?;
    println!("{:?}", catalog.entry("CTH"));
    Ok(())
}