PLC profiles

Intro

The kvhostlink-connection node stores a canonical PLC profile value. Use the lowercase value from the table; legacy labels such as KV-X500 are rejected.

Supported PLC profiles

Canonical profile Intended KV family Addressing note
keyence:kv-nano KV Nano Standard profile.
keyence:kv-nano-xym KV Nano XYM-style profile.
keyence:kv-3000 KV-3000 Standard profile.
keyence:kv-3000-xym KV-3000 XYM-style profile.
keyence:kv-5000 KV-5000 Standard profile.
keyence:kv-5000-xym KV-5000 XYM-style profile.
keyence:kv-7000 KV-7000 Standard profile.
keyence:kv-7000-xym KV-7000 XYM-style profile.
keyence:kv-8000 KV-8000 Standard profile.
keyence:kv-8000-xym KV-8000 XYM-style profile.
keyence:kv-x500 KV-X500 Standard profile.
keyence:kv-x500-xym KV-X500 XYM-style profile.

How to configure the connection node

Field Example Description
Name KV Host Link TCP Editor display name.
Host 192.168.250.100 PLC IP address or host name.
Port 8501 Host Link TCP/UDP port.
Transport tcp tcp or udp.
Timeout ms 3000 Response timeout in milliseconds.
PLC Profile keyence:kv-x500 Canonical PLC profile value.

Model-specific cautions

Common address validation is protocol-wide. If an address is valid for the common Host Link family but outside your PLC model's actual range, the PLC response is returned as the runtime error.

Timer/counter preset writes use Host Link WS and WSS. Those commands are documented for KV-8000/7000-series CPU units; other CPU units may return PLC error E1.

AT digital trimmer reads were verified on KV-7500, but KV-X500 does not have AT digital trimmer access. The high-level write helpers reject AT before sending.