Getting started

Start here

This page gets you from an empty Python project to your first KEYENCE KV Host Link read. You will choose the canonical profile keyence:kv-7000, connect to your PLC at 192.168.250.100:8501, read DM0, then write and restore a test register.

Prerequisites

Requirement Value
Python Python 3.10 or newer.
PLC network Your KV PLC must be reachable from your PC.
Host Link port Use port 8501 for TCP or UDP unless your PLC connection node is configured differently.

Install

pip install kv-hostlink

Choose profile

from hostlink import device_range_catalog_for_plc_profile


def main() -> None:
    catalog = device_range_catalog_for_plc_profile("keyence:kv-7000")
    print(catalog.plc_profile)


if __name__ == "__main__":
    main()

Use the exact canonical profile string that matches your PLC model. The library does not infer the device range catalog from the PLC model response.

First read

import asyncio
from hostlink import HostLinkConnectionOptions, device_range_catalog_for_plc_profile, open_and_connect, read_typed


async def main() -> None:
    catalog = device_range_catalog_for_plc_profile("keyence:kv-7000")
    options = HostLinkConnectionOptions(host="192.168.250.100", port=8501)
    async with await open_and_connect(options) as client:
        dm0 = await read_typed(client, "DM0", "U")
        print(f"DM0 = {dm0}")


if __name__ == "__main__":
    asyncio.run(main())

Expected output:

DM0 = 123

Your number will match the current value stored in DM0 on your PLC.

First write

import asyncio
from hostlink import HostLinkConnectionOptions, open_and_connect, read_typed, write_typed


async def main() -> None:
    options = HostLinkConnectionOptions(host="192.168.250.100", port=8501)
    async with await open_and_connect(options) as client:
        test_address = "DM100"
        original = await read_typed(client, test_address, "U")
        try:
            await write_typed(client, test_address, "U", 1234)
            readback = await read_typed(client, test_address, "U")
            print(f"{test_address} = {readback}")
        finally:
            await write_typed(client, test_address, "U", original)


if __name__ == "__main__":
    asyncio.run(main())

Only write to a test address that is safe for your machine and program.

Confirm success

  1. The profile snippet prints keyence:kv-7000.
  2. The connection opens without a timeout.
  3. The first read prints a value for DM0.
  4. The write example prints the value written to DM100.
  5. The finally block restores the original test-register value.

If it does not work

Symptom Check
The connection fails immediately. Default port is 8501, not 1025; double-check the connection node port.
Profile selection fails. Use one of the exact strings in PLC profiles; aliases and combined old names are rejected.
Reads fail while you are trying the first example. Start with DM word reads; do not start with timer/counter or expansion buffer access.
Timer/counter preset writes return E1. Timer/Counter preset writes (WS/WSS) are only supported on KV-8000/7000-series.

Next pages

Continue with Usage guide, then check PLC profiles, Supported registers, and Gotchas.