Device Range Catalog

This document replaces plc_device_range_registers - base.csv.

This catalog is a connected-diagnostics catalog, not an editor-side address range validator. It is only accurate after a PLC profile has been selected and the client can read the profile-specific registers or apply a fixed profile rule. Node-RED uses the supported/unsupported device-code part of this table to avoid sending clearly unsupported device codes for a selected profile, but it does not pre-check PLC model-specific address upper bounds.

The library now owns the device-range rules in source code and reads live upper bounds from the PLC itself after the caller chooses the PLC profile:

  1. caller selects SlmpPlcProfile
  2. read the profile-specific SD register window
  3. build a SlmpDeviceRangeCatalog with point counts and 0-based address ranges

The standard high-level API does not auto-resolve the profile through ReadTypeNameAsync(), model text, or model code. ReadTypeNameAsync() is diagnostic information only. Some PLCs or communication paths cannot return a reliable type name, and a wrong inference can select the wrong address grammar or range catalog. Keep PLC profile selection explicit in configuration or UI. ReadDeviceRangeCatalogAsync() reads the configured profile only.

PointCount is the usable point count reported by the PLC or by a fixed family rule. UpperBound is the inclusive last address, so for 0-based devices it is PointCount - 1. AddressRange is preformatted text such as X000-X1FF.

Supported = false means the family does not expose that device. Supported = true with PointCount = null means the PLC profile supports the device but does not publish a finite bound register. Family-aware string parsing also rejects DX and DY for SlmpPlcProfile.IqF before transport.

API

Both SlmpClient and QueuedSlmpClient expose the standard connected-profile catalog method.

Method Use
ReadDeviceRangeCatalogAsync(CancellationToken cancellationToken = default) Read the catalog for the client profile selected in SlmpConnectionOptions.

Example:

using PlcComm.Slmp;

var options = new SlmpConnectionOptions("192.168.250.100", SlmpPlcProfile.IqF)
{
    Port = 1025,
};

await using var client = await SlmpClientFactory.OpenAndConnectAsync(options);
var catalog = await client.ReadDeviceRangeCatalogAsync();

Console.WriteLine($"selected={catalog.Model} -> {catalog.PlcProfile}");
foreach (var entry in catalog.Entries)
{
    if (!entry.Supported) continue;
    Console.WriteLine(
        $"{entry.Device}: points={entry.PointCount}, range={entry.AddressRange}, source={entry.Source}");
}

Returned types:

  • SlmpDeviceRangeCatalog
  • SlmpDeviceRangeEntry
  • SlmpPlcProfile
  • SlmpDeviceRangeCategory
  • SlmpDeviceRangeNotation

SlmpDeviceRangeEntry.Notation uses Base10, Base8, or Base16 for the public address text this library expects.

If you need an explicit low-level override, both clients also expose another overload.

Method Use
ReadDeviceRangeCatalogAsync(SlmpPlcProfile plcProfile, CancellationToken cancellationToken = default) Read a catalog for a canonical profile other than the client's configured profile.

That overload is for reading the catalog for a canonical profile other than the client's configured profile. It is not the standard application route.

Embedded profile rules cover:

  • IqR
  • IqL
  • MxF
  • MxR
  • IqF
  • QCpu
  • LCpu
  • QnU
  • QnUDV

Range Rules

Addr is the library-facing address notation, not necessarily the notation used in MELSEC manuals.

For iQ-R-series range rows, the SD register value is the PLC-configured current point count. The catalog must cap that value at the iQ-R-series maximum below, then derive UpperBound = PointCount - 1. In other words, use PointCount = min(SD point count, MaxPointCount) for the rows listed here. The iQ-R-series 0002/0003 device access format uses a 4-byte device number, so these maximum addresses are representable by the protocol format.

Item Devices Max address MaxPointCount Setting unit
X X X2FFF 12288 (0x3000) n/a
Y Y Y2FFF 12288 (0x3000) n/a
M M M94674943 94674944 (0x5A4A000) 64 points
B B B5A49FFF 94674944 (0x5A4A000) 64 points
F F F32767 32768 64 points
SB SB SB5A49FFF 94674944 (0x5A4A000) 64 points
V V V32767 32768 64 points
L L L32767 32768 64 points
T TS, TC, TN T5259711 5259712 32 points
ST STS, STC, STN ST5259711 5259712 32 points
LT LTS, LTC, LTN LT1479295 1479296 1 point
LST LSTS, LSTC, LSTN LST1479295 1479296 1 point
C CS, CC, CN C5259711 5259712 32 points
LC LCS, LCC, LCN LC2784543 2784544 32 points
D D D5917183 5917184 (0x5A4A00) 4 points
W W W5A49FF 5917184 (0x5A4A00) 4 points
SW SW SW5A49FF 5917184 (0x5A4A00) 4 points
Item Devices Addr iQ-R MX-F MX-R iQ-F QCPU LCPU / QnU / QnUDV
X X base16 SD260-SD261 SD260-SD261 SD260-SD261 SD260-SD261 SD290 SD290
Y Y base16 SD262-SD263 SD262-SD263 SD262-SD263 SD262-SD263 SD291 SD291
M M base10 SD264-SD265 SD264-SD265 SD264-SD265 SD264-SD265 SD292, clip 32768 SD286-SD287
B B base16 SD266-SD267 SD266-SD267 SD266-SD267 SD266-SD267 SD294, clip 32768 SD288-SD289
SB SB base16 SD268-SD269 SD268-SD269 SD268-SD269 SD268-SD269 SD296 SD296
F F base10 SD270-SD271 SD270-SD271 SD270-SD271 SD270-SD271 SD295 SD295
V V base10 SD272-SD273 SD272-SD273 SD272-SD273 n/a SD297 SD297
L L base10 SD274-SD275 SD274-SD275 SD274-SD275 SD274-SD275 SD293 SD293
S S base10 SD276-SD277 n/a n/a n/a SD298 SD298
D D base10 SD280-SD281 SD280-SD281 SD280-SD281 SD280-SD281 SD302, clip 32768 SD308-SD309
W W base16 SD282-SD283 SD282-SD283 SD282-SD283 SD282-SD283 SD303, clip 32768 SD310-SD311
SW SW base16 SD284-SD285 SD284-SD285 SD284-SD285 SD284-SD285 SD304 SD304
R R base10 SD306-SD307, clip 32768 SD306-SD307, clip 32768 SD306-SD307, clip 32768 SD304-SD305 fixed 32768 SD306-SD307, clip 32768
T TS, TC, TN base10 SD288-SD289 SD288-SD289 SD288-SD289 SD288-SD289 SD299 SD299
ST STS, STC, STN base10 SD290-SD291 SD290-SD291 SD290-SD291 SD290-SD291 SD300 SD300
C CS, CC, CN base10 SD292-SD293 SD292-SD293 SD292-SD293 SD292-SD293 SD301 SD301
LT LTS, LTC, LTN base10 SD294-SD295 SD294-SD295 SD294-SD295 n/a n/a n/a
LST LSTS, LSTC, LSTN base10 SD296-SD297 SD296-SD297 SD296-SD297 n/a n/a n/a
LC LCS, LCC, LCN base10 SD298-SD299 SD298-SD299 SD298-SD299 SD298-SD299 n/a n/a
Z Z base10 SD300 SD300 SD300 SD300 fixed 10 fixed 20
LZ LZ base10 SD302 SD302 SD302 SD302 n/a n/a
ZR ZR base10 SD306-SD307 SD306-SD307 SD306-SD307 n/a open SD306-SD307
RD RD base10 SD308-SD309 SD308-SD309 SD308-SD309 n/a n/a n/a
SM SM base10 fixed 4096 fixed 10000 fixed 4496 fixed 10000 fixed 1024 fixed 2048
SD SD base10 fixed 4096 fixed 10000 fixed 4496 fixed 12000 fixed 1024 fixed 2048

Notes

  • QCPU D and W exclude the extended area and are clipped to 32768.
  • QCPU ZR remains supported, but there is no finite upper-bound register, so the catalog reports Supported = true, PointCount = null, and AddressRange = null.
  • LCPU, QnU, and QnUDV share the same range-register layout in this implementation.
  • Z on LCPU, QnU, and QnUDV is treated as the fixed Z0-Z19 family limit. QnUDV was live-checked on 2026-05-01: Z19 read successfully and Z20 returned 0x4031.
  • ZR and R on LCPU, QnU, and QnUDV are runtime-limited by probing readable ZR addresses. QnUDV was live-checked on 2026-05-01 with ZR393215 accepted, ZR393216 returning 0x4031, R32767 accepted, and R32768 returning 0x4031.
  • iQ-F X and Y are documented in MELSEC manuals with octal addressing. This library emits Base8 and formats ranges such as X0000-X1777.