Supported registers

This page lists device families supported by the high-level API.

The high-level string parser accepts plain device strings only. The examples below are address syntax examples, not guaranteed range limits for every PLC model.

Bit device families

Family Kind Example address Notes
X Input relay X10 Hexadecimal address.
Y Output relay Y10 Hexadecimal address.
M Internal relay M100 Decimal address.
L Latch relay L100 Decimal address.
SM Special relay SM100 Decimal address.
F Annunciator F100 Decimal address.
V Edge relay V100 Decimal address.
B Link relay B100 Hexadecimal address.
TS, TC Timer contact / coil TS0 Decimal address.
STS, STC Retentive timer contact / coil STS0 Decimal address.
CS, CC Counter contact / coil CS0 Decimal address.
SB Link special relay SB100 Hexadecimal address.
S Step relay S100 Decimal address.
DX, DY Direct access input/output DX10 Hexadecimal address.
LTS, LTC Long timer contact / coil LTS0 Decimal address.
LSTS, LSTC Long retentive timer contact / coil LSTS0 Decimal address.
LCS, LCC Long counter contact / coil LCS0 Decimal address.

Word device families

Family Kind Example address Notes
D Data register D100 Decimal address.
SD Special register SD100 Decimal address.
W Link register W100 Hexadecimal address.
TN Timer current value TN0 Decimal address.
STN Retentive timer current value STN0 Decimal address.
CN Counter current value CN0 Decimal address.
SW Link special register SW100 Hexadecimal address.
LTN Long timer current value LTN0 Decimal address; treated as double-word in random helpers by default.
LSTN Long retentive timer current value LSTN0 Decimal address; treated as double-word in random helpers by default.
LCN Long counter current value LCN0 Decimal address; treated as double-word in random helpers by default.
LZ Long index register LZ0 Decimal address; treated as double-word in random helpers by default.
Z Index register Z0 Decimal address.
R File register R0 Decimal address.
RD Module access register RD0 Decimal address.
ZR File register ZR0 Decimal address.

Addressing notes

Topic Current behavior
Plain device string Supported. Use forms such as D100, M100, X10, W100, LZ0.
Hexadecimal address families X, Y, B, W, SB, SW, DX, and DY parse their numeric part as hexadecimal.
:D / :F suffix Not supported by the current high-level parser. Use typed C++ fields such as double_word where available.
.n bit-in-word suffix Not supported by the current high-level parser.
Long timer/counter restrictions Some random and multi-block operations reject long contact/coil devices. Check Status and use simpler contiguous operations first.

Profile-specific range limits depend on the PLC family and serial module. See PROFILES.md before choosing the final profile for a live system.